LST Smoke Alarm IBSOU DD P01 User Manual

Integrated Base Sounder  
IBSOU-DD-P01, IBSOU-DD-P02  
• ADM loop technology with  
System Sensor/200 protocol  
• Can be activated with two different  
tone types, 32 tone types selectable  
• Sound level selectable in three steps  
– up to 95dB(A)  
• Low power consumption  
• Versions with or without integrated  
dual-isolator available  
• Two base types available – IP24, IP44  
Description  
The loop powered sounder incorporates a detector The sound level can be selected in 3 steps. The address  
base and is fitted into a round, white plastic case. It is of the sounder is selected with two decadic rotary swit-  
powered and actuated as a module through the ADM ches located at the bottom of the device.  
loop with System Sensor/200 protocol. Fire Detectors  
Series 200 can be fitted into the integrated base.  
The base sounder is designed for indoor surface moun-  
ting. For this purpose a special base is needed. Two  
The sounder can be activated by a Fire Detection Con- different base types for protection classes IP24 or IP44  
trol Panel Series BC216 with two different tone types, are available, depending on the application. An optional  
depending on the parameter setup. One of 32 different mounting plate can be supplied for surface mounted  
tone type combinations can be selected with a DIL- cabling.  
switch. The following tones are available, for example:  
• Continuous tone 660Hz,  
The sounder is available in two different versions: With  
or without integrated dual-isolator module.  
• Emergency signal according to DIN 33404,  
• Slow whoop tone according to NEN 2575,  
• Alternating tone 800/970Hz, and many more.  
Specifications  
Operating voltage  
Supply through loop voltage  
Sound level (detector installed)  
typ. 70dB(A) at 1m distance (low)  
typ. 79dB(A) at 1m distance (medium)  
typ. 87dB(A) at 1m distance (high)  
max. 95dB(A) at 1m distance (high)  
Ambient temperature  
Dimensions ø × H  
Weight  
-25°C to +70°C  
112 × 42 (mm) (without detector, incl. base LPBW)  
134g  
Colour  
cream, RAL 9001  
Building Safety. Building Security.  
A
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27  
IBSOU-DD-P0x_DBL_LST_EN_0804.PDF • PAGE 1  
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED  
 

KTM Automobile Parts EXC User Manual
Lenovo Laptop B475E User Manual
Lenovo Server 6431 User Manual
Lenoxx Electronics Stereo System PR 355 User Manual
Liebert Network Card XDK User Manual
Manitowoc Ice Switch K00108 User Manual
Master Lock Portable Generator MGR2900A MGR4500I MGR6000I User Manual
Maytag Range MER6755AAS26 User Manual
Melissa Beverage Dispenser 758039 User Manual
Melissa Iron 641050 User Manual